3.8 Closed Loop Control

Closed loop control is only possible when an OPm2 or a serial link is connected to the CombiDrive

®

.

3.8.1 General Description

The CombiDrive

®

provides a Proportional/Integral (PI) control function for closed loop control (see Figure 7). PI

control is ideal for temperature or pressure control, or other applications where the controlled variable changes
slowly or where transient errors are not critical. This control loop is not suitable for use in systems where fast
response times are required.

Note:

The closed loop function is not designed for speed control, but can be used for this provided that fast
response times are not required.

When closed loop PI control is enabled (P201 = 002), all setpoints are calibrated between zero and 100%, i.e.
a setpoint of 50.0 = 50%. This allows general purpose control of any process variable that is actuated by motor
speed and for which a suitable transducer is available.

Setpoint

Scaling

P211, P212

Feedback

Sample

Rate

P205

Low Pass

Filter

P206

P

P202

I

P203, P207

Acceleration/

Deceleration

Ramp

P002, P003

Motor

M

Process

e.g. fan

Transducer

P208

+

P201 = 000

Feedback

(e.g. duct pressure)

P201 = 002

Closed Loop Mode Disabled

Closed Loop Mode Enabled

P210

Feedback

Monitor

Figure 7: Closed Loop Control

3.8.2 Hardware Setup

Connect the signal wire from the external feedback transducer to control terminal 10. Set jumper JP303 if
voltage input type is required (default) or set JP302 if current input type is required.

15 V dc power for the feedback transducer can be supplied from control terminal 8.

3.8.3 Parameter Settings

Closed loop control cannot be used unless P201 is first set to 001. Most of the parameters associated with
closed loop control are shown in Figure 7. Other parameters which are also associated with closed loop
control are as follows:

P001 (value = 007)
P061 (value = 012 or 013)
P210
P220

Descriptions of all closed loop control parameters are provided in section 4. For further detailed information
about PI operation, refer to the Siemens DA 64 Catalogue.