Installation and Start-Up

2.1

Site Preparation

2.1.1

Mounting Instructions

To securely mount TimeVault in any EIA standard 19-inch (48.26-cm) rack system, use
the equipment supplied in Symmetricom’s Rack Mount Kit and follow the steps outlined
below.

The Rack Mount Kit contains:

• 2 mounting brackets (part number 206-719)

• 4 flat-head, Phillips screws (part number 241-008-005, 8-32 x 5/8)

To rack mount TimeVault:

1. Remove and discard the two factory-installed flat head (Phillips) screws from the front

end of a TimeVault side panel.

2. Place a rack mount bracket on the side panel, so that the countersunk screw holes in

the bracket line up with the screw holes in the panel.

3. Place 2 flat-head Phillips screws from the Rack Mount Kit through the holes in the

bracket and into TimeVault.

4. Tighten the screws to the following specifications:

Use a #2 size Phillips bit with an inch ounce torque setting of 4 ¼ to 4 ¾ (high).

5. Repeat steps 1-4 to install the other rack mount bracket on the unit’s other side panel.

Replace the factory-installed
screws with screws from
the Rack Mount Kit