2 details of each of the parameters, 2) token monitor time (parameter address 04(8)), 2 details of each of the parameters -2 – Sharp Z-336J User Manual

Page 140

Advertising
background image

12-2

Chapter 12: Parameters

12

12-2 Details of each of the parameters

(1) Enable/disable the use of the transmission buffer (Setting parameter address 37

(8)

)

Select whether to enable/disable the buffer for each message by entering the appropriate value at
parameter address 37

(8)

.

* 80 to 83

(H)

are the valid values for parameter address 37

(8)

.

Relationship between messages and transaction codes.

(2) Token monitor time (parameter address 04

(8)

)

Set the token monitor time as follows, based on the number of bytes being sent by this station.
- 0 to 5K bytes: 10 ms
- 5K to 10K bytes: 30 ms
- 10K bytes or more: 40 ms

Message

Selection of

transmission buffer

80

(H)

81

(H)

82

(H)

83

(H)

Message other than transmission

Transmission

message

Messages other than SHARP's proprietary
message format

SHARP's
proprietary format

Computer link function

Remote function

Message

Transaction code (TCD)

Use selection of

transmission type buffer

80

(H)

81

(H)

82

(H)

83

(H)

Messages

other than
transmission

60000 to 65202 (request)

X

X

X

X

65203 to 65215 (response)

X

O

X

O

Transmission

messages

0 to 999

O

O

O

O

1000 (request computer link function: SHARP's

proprietary function)

X

X

O

O

1001 (request remote function: SHARP's proprietary

function)

X

X

O

O

1002 to 1199

O

O

O

O

1200 (response of computer link function: SHARP's

proprietary function)

O

O

O

O

1201 (response of remote function: SHARP's

proprietary function)

X

X

O

O

1202 to 59999

O

O

O

O

*

(Transmission buffer...

: Used,

: Not used)

*

(Transmission buffer...

: Used,

: Not used)

Advertising