3 how to set parameters, 1] when the jw-20fl5/20flt or z-366j is used, 3 how to set parameters -3 – Sharp Z-336J User Manual

Page 141: 1] when the jw-20fl5/20flt or z-366j is used -3

Advertising
background image

12-3

Chapter 12: Parameters

12

12-3 How to set parameters

[1] When the JW-20FL5/20FLT or Z-366J is used

Set parameters of JW-20FL5/20FLT and Z-336J as optional parameters of the control module (CPU
board). Determine the area of the optional parameters using the module No. switch set value of JW-
20FL5/20FLT and Z-336J. The parameters occupy 64 bytes per module.

How to set the parameters using the JW-14PG

This paragraph describes param-
eter setting procedures (in system
memory) using the hand-held pro-
grammer JW-14PG.

1

Connect the JW-14PG to the

PG port on the control module
(CPU board.)

2

Set the PC to program mode.

3

Set to the initial mode (parameter setting).

4

Select the option parameter and enter "2" for the module

No. switch number.

5

Rewrite start switch to 00

(H)

.

Reading parameter address 77

(8)

.

6

Enter IP address (192.168.250.3) for the parameter address 00 to 03

(8)

.

Decimal notation of parameter 00.

Same as the above, enter the other parameter addresses.

Connection cable

(JW-22KC/24KC)

JW-14PG

Control module (JW-33CUH)

JW-20FL5

(The modules shown below

are installation examples)

Decimal display of the setting
of parameter 00

JW-14PG screen

75

HEX

00

76

HEX

00

I Parameter 0 - SW: 2

>77

HEX

00

01

DCM

168

02

DCM

250

I Parameter

>03

DCM

003

FL-net module Host PC

Control module

JW-20FL5

JW-20FLT

JW20H

JW-21CU/22CU

JW30H

JW-31CUH1

JW-32CUH1

JW-33CUH1/2/3

FL-net

board

Host J-board

CPU board

Z-336J

Z-300 series Z-311J/312J/313J

Z-500 series Z-511J

- Relationship between the host PC and the con-

trol module

Note: Do not set switch SW3 outside the

range of 0 to 6.

Module No. switch

setting value

Parameter address

(H)

0

00 to 77

1

00 to 77

2

00 to 77

3

00 to 77

4

00 to 77

5

00 to 77

6

00 to 77

Reading a prameter address

(H)

I Parameter 0 - SW: 2

I Parameter

0) I/O

1) Option

Advertising