4 error indicators on the display panel, 4 error indicators on the display panel -6 – Sharp Z-336J User Manual

Page 149

Advertising
background image

13-6

Chapter 13: Troubleshooting

13

13-4 Error indicators on the display panel

If an error occurs while communicating with the module, the error details can be checked by reading
the error code on the display panel (LED display) of the module. Find the cause of the error by looking
up the error code that is displayed. Then take the appropriate countermeasures (resetting the param-
eters, etc.)

LED symbol

Details

JW-20FL5/T
Z-336J

JW-50FL

LN

LNK

Lit when communicating normally.

TX

TX

Lit when sending data.

RX

RX

Lit when receiving data.

12 V

12 VDC

Lit when 12 VDC power is present. (This indicator cannot be used with JW-20FLT.)

T

TEST

Lights while in the test mode. (Is normally OFF.)

PE

PER

Lights when the parameter settings are abnormal.

HE

HER

Lights when the module has an error.

S0 to S7

S0 to S7 Displays the node number when it is normal, and an error code when an error occurs.

LED name

Error

code

(H)

Error item

Cause (parameter setting status)

S7 S6 S5 S4 S3 S2 S1 S0

O

O

O

O

O

O

O

01

Node number

Node number is outside the range of 1

to 254.

O

O

O

O

O

O

O

02

Token monitor time

The token monitor time is 0.

O

O

O

O

O

O

O

04

Not available CU
(Only the JW-50FL.)

The host PC is a W70H/100H.

O

O

O

O

O

O

O

08

Area 1 address

Area 1 is outside the allowed range.

*

O

O

O

O

O

O

09

Area 1 size

Area 1 is larger than 8K bits.

O

O

O

O

O

O

0A

Area 2 address

Area 2 is outside the allowed range.

O

O

O

O

O

0B

Area 2 size

Area 2 is larger than 8K words.

O

O

O

O

O

0E

Area 1 PC address

The top address of area 1 is outside
the allowed range.

O

O

O

O

0F

Area 2 PC address

The top address of area 2 is outside
the allowed range.

O

O

O

O

O

O

O

10

Doubled node
number

The same node number was assigned
to more than one node.

O

O

O

O

O

O

11

Doubled common
memory address

This node's transmission area 1 (or
2) is used by another node.

*

O

O

O

O

O

O

O

20

Range of area 1

*

When the JW20H and J-board (Z-300
series) is used for a PC, any area is set
for file 1 though there is no file 1.

O

O

O

O

O

O

21

Range of area 2

O

O

O

O

O

O

22

Range of each table

O

O

O

O

O

23

Rang e of the

transmission buffer.

JW-20FL5

S0
S1
S2
S3
S4
S5
S6
S7

HE
PE

T

12V

RX

TX
LN

(JW-50FL)

JW-50FL

S0
S1
S2
S3
S4
S5
S6
S7

LNK

TX

RX

DC12V

TEST

PER

HER

(JW-20FLT)

(JW-20FL5)

(Z-336J)

: Light,

: Light off

Error code of LED (S0 to S7)

* Related to the cyclic transfer

Advertising
This manual is related to the following products: