2 jw-20flt, 2 jw-20flt -2 – Sharp Z-336J User Manual

Page 15

Advertising
background image

4-2

Chapter 4: Name and Function of Each Part

4

4-2 JW-20FLT

ON

OFF

S

H

I

E

L

D

1

Display panel

2

Connector for programmer

3

Connector for 10BASE-T

6

Reset switch

Connector for shield
switch for 10BASE-T

5

Module No. switch

(Factory setting: 0)

(Factory setting: ON)

(Front) (Rear)

4

Name

Function

1

Display panel

Displays the JW-20FLT operating status using LEDs.

LN

Lights when communicating normally.

TX

Blink at transmitting data.

RX

Blink at receiving data.

12 V

Cannot be used with the JW-20FLT.

T

Lights at test mode. (Normally, this is not used.)

PE

Lights at parameter setting error.

HE

Lights at this module error.

S0 to S7

Displays the station number when operating normally. Displays an error

code if an error occurs.

2

Connector for programmer

Connect a JW-14PG programmer or similar equipment to set the
parameters on the JW-20FLT.

3

Connector for 10BASE-T

Connect the 10BASE-T twisted pair.

4

Connector for
Shield switch

for 10BASE-T

ON

The shield on the twisted pair cable will be shorted to the FG (base) of
this module.

OFF

The shield on the twisted pair cable is not shorted to the base.

5

Module No. switch

Specify a module number from 0 to 6.
- Be careful do not use the same number for another option module.

6

Reset switch

Only used by SHARP engineers. Users should not press this switch.

Advertising
This manual is related to the following products: