3 jw-50fl, 1] general specifications, 2] communication specifications – Sharp Z-336J User Manual

Page 153: 3 jw-50fl -4, 1] general specifications -4, 2] communication specifications -4

Advertising
background image

14-4

Chapter 14: Specifications

14

14-3 JW-50FL

[1] General specifications

*1: The JW-50FL cannot be installed on a W70H/100H.

[2] Communication specifications

(1) Communication section specifications

*2: Maximum transfer distance between stations when connecting more than one segment using re-

peaters.

*3: Maximum transfer distance between stations when connecting more than one 10BASE-T segment

using hubs.

Item

Specifications

Host PC

Install in optional slots on the JW50/70H/100H (max. 5 units) *1

Storage temperature

-20 to +70˚ C

Ambient operating
temperature

0 to +55˚ C

Ambient humidity

35 to 90% RH (without condensing)

Vibration resistance

Equivalent to JIS C 0911: Vibration test: width 0.15 mm (10 to 58
Hz), 9.8 m/s

2

(58 to 150 Hz), (2 hours each on the X, Y, Z axes)

Impact resistance

Equivalent to JIS C 0912: 98 m/s

2

(3 each on the X, Y, Z axes)

Internal current consumption

(5 VDC)

400 mA

External supply power

12 VDC ±5%, 0.5 A (only needed for 10BASE5 systems)

Ethernet interface

AUI for 10BASE5 (D-sub 15-pin)

10BASE-T (RJ-45 connector)

Programmer interface

D-sub 25-pin

Weight

Approx. 380 g

Accessory

One cable, one instruction manual

Item

Specifications

Network compatibility

10BASE5 or 10BASE-T

Transfer speed

10M bps

Physical topology

Bus (10BASE5) / Star (10BASE-T)

Transfer media

50 ohm yellow cable (10BASE5), twisted pair cable (10BASE-T)

Transfer system

Base band

Maximum transfer distance

10BASE5: 500 m/segment, 2.5 km/network *2
10BASE-T: 100 m/segment, 500 m/network *3

Protocol configuration

Application
Transport

Network
Data link

FA link protocol
UDP
IP
Ethernet V2

Advertising