15-7 Grounding the FL-net system

[1] Outline of the grounding procedures for the FL-net system

This section uses an example of how to ground an FL-net controller control panel when attaching the
control panel to the steel frame of a building.
In order to ground the control panel to a building frame, the following conditions need to be satisfied. If
the ground cannot meet the conditions below, provide an exclusive class D ground for the controller.
1. All of the steel frames must be welded to each other.
2. Class D grounding standards must be met between the controller ground and the steel frame.
3. No strong electrical current should flow through the ground terminal on the controller.
4. Keep a distance of 15 m or more between the controller ground point and any ground for a high

current electrical power panel.

An example of how to ground a control panel: 1 (grounded to the steel frame of a building)

An example of how to ground a control panel: 2 (exclusive class D ground)

Keep a distance of 15 m or more

Control

panel

Building's steel frame

Contact point on

the steel frame

High current

panel

High current

panel

Control

panel

PLC etc.

Steel frame of

a building

Contact point on

the steel frame