15-60

Chapter 15: Appendix

15

[3] Wiring the power lines and grounding the network equipment in an FL-net

This section describes how to wire the power lines and ground lines for the network equipment in an FL-
net system.
When wiring power lines and making ground connections, observe the precautions below.
1. Connect the coaxial cable ground terminal to the class D ground that is specially created for the

controller.

2. Connect the frame ground of the hubs for a 10BASE-T system to the class D ground that is specially

created for the controller. Supply power to the hub from an isolation transformer with a static electric-
ity protective function (used to power the controller).

3. Provide an exclusive class D or better ground for the controller FG (frame ground) terminal. Do not

connect this terminal to the controller frame.

4. Connect the FG (frame ground) terminal of FL-net modules to the FG (frame ground) of the controller.
5. Connect the shield ground on the transceiver (AUI) cable to the FG (frame ground) terminal on the

FL-net module.

6. When a transceiver (AUI) needs DC power (12 VDC etc.), provide a stable power supply for exclusive

use by the network, and connect the DC output terminals to the FL-net module. 100 VAC input power
needs to be supplied from the isolation transformer, the same as for the controller.

Example of how to wire power lines and ground lines for network equipment in the FL-net system

Coaxial cable

Transceiver

Ground terminal

Hub

Transceiver
cable
(AUI cable)

Isolation
transformer with
static electricity
protective function

100 VAC

Class D ground

100 VAC

12 VDC power
for AUI

Class D ground
exclusively for use
by the controller