background image

3 Installation and Commissioning

B3L−12

CP 343-1 Lean for Industrial Ethernet / Manual Part B3L

Release 03/2007

C79000-G8976-C198-04

Slider for setting

the chassis

ground contact

Attachment to Industrial

Ethernet:

2 x 8-pin RJ-45 jack

Figure 3-1

Connectors of a CP 343−1 Lean with the Front Panel Open

Ground/Chassis Ground Concept

Notice
Please note the instructions regarding the grounding and chassis ground concept
in the SIMATIC S7 installation guides; see “SIMATIC S7 Programmable Controller
S7−300 − Installation and Hardware: Installation Manual” /1/.

Behind the hinged panel on the left of the device, you will see a slider with which
you can connect or disconnect the chassis ground of the 24 V power supply with
reference ground.

S Slider pushed in: chassis and reference ground connected (note: the slider

must be felt to lock in place).

S Slider pulled out: No connection between chassis and reference ground.
When shipped: Slider pushed in

Use a screwdriver to set the slider.

Note
An Ethernet cable can also be inserted and removed with the power supply on.