9 Further Notes on Operation

B3L−46

CP 343-1 Lean for Industrial Ethernet / Manual Part B3L

Release 03/2007

C79000-G8976-C198-04

9 Further Notes on Operation

9.1

Memory Reset

Available Functions

The CP has a two-level function available for resetting memory:

S Clear / reset

Following this memory reset, the CP retains the preset MAC address and the

retentive parameters. The CP is therefore immediately ready for downloads

using the IP address.
The retentive parameters include:
− IP address, subnet mask and, if applicable, router address
− LAN settings

S Resetting to factory settings

After this memory reset, the CP retains only the factory-set MAC address (as

shipped).

Note
Using the functions described here to reset the memory, you do not modify the

configuration data on the CPU!
If you subsequently upload the configuration data from the CPU to a PG you will

always obtain the configuration data that were previously on the CP (with

parameters, connections, IP address).

How to Use the Function

You can start the memory reset functions in STEP 7.

S Clear / reset

In STEP 7 / /HW Config with PLC

"

Clear/Reset

or
In STEP 7 / NCM Diagnostics with Operating Mode

"

Clear/Reset Module

S Factory defaults reset

In STEP 7 / NCM Diagnostics with Operating Mode

"

Reset to Factory

Defaults