IM-215 Rev-A.1 Series Innova-Switch™ Page 26 of 42

following procedure can be used to verify preliminary operation.

1. Remove the instrument enclosure cover by turning counter clockwise to expose

the LS3200 Switch

electronics.

2. Turn on power at its source.

3. Observe that either the red or green LED comes on.

4. If neither lamp illuminates refer to the trouble shooting Section, 6.2.


5.2

L.E.D. and Relay Status Logic (Fail-Safe)


5.2.1

The L.E.D.s (Red and Green) are an indication of the sensors status (ie. dry or wet)
and are not affected by the position of the fail-safe jumper J-2. The fail-safe jumper J-
2 changes the relay activation status allowing the user to select the fail-safe power off
condition most appropriate to the application. Refer to the tables below that show the
logic conditions between the sensors, L.E.D. lights, relay coil and contacts for each
position of the fail-safe jumper J-2.


5.2.2

Normal Operation (as set at factory)


The switch comes configured from the factory with the following operation with the J-2
jumper in the B (2-3) position. (Refer to Figure 8.0.)

RELAY

RED GREEN

RELAY

CONTACT

SENSOR STATUS

LED

LED

COIL STATUS

STATUS


Dry, or Lower Thermal

o NC

Dispersion Fluid

ON

OFF

Activated

(ie. hydrocarbons)

o NO

Wet, or Higher Thermal

o NC

Dispersion Fluid

OFF

ON

Deactivated

(ie. water)

o NO
















5.2.3

Alternate Operation (Field Selectable)


The relay logic may be reversed by moving the J-2 jumper to position A(1-2). (Refer
to Figure 8.0.)

RELAY

RED GREEN

RELAY

CONTACT

SENSOR STATUS

LED

LED

COIL STATUS

STATUS


o NC

Dry, or Lower Thermal

ON

OFF

Deactivated