2 electrical connections, 3 load lead connections – Kohler Generator Sets 20--2800 kW User Manual

Page 48

Advertising
background image

TP-5700 7/93

36

Section 7 Electrical Requirements

7.2 Electrical Connections

Several electrical connections must be made between
the generator set and other components of the system
for proper operation. Because of the large number of
accessories and possible combinations, this manual
does not address specific applications. Refer to the
submittal catalog accessory drawings and wiring
diagrams

for

connection

and

location.

Most

field-installed

accessory

kits

include

installation

instructions.

For

customer-supplied

wiring,

select

the

wire

temperature rating in Figure 7-2 based upon the
following criteria:

D

Select row 1, 2, 3, or 4 if the circuit rating is

110 amperes or less or requires #1 AWG (42.4 mm

2

)

or smaller conductors.

D

Select row 3 or 4 if the circuit rating is greater than

110 amperes or requires #1 AWG (42.4 mm

2

) or

larger conductors.

Comply with applicable national and local codes when
installing a wiring system.

Row

Temp. Rating

Copper (Cu) Only

Cu/Aluminum (Al) Combinations

Al Only

1

60

_C (140_F)

or

75

_C (167_F)

Use No. * AWG, 60

_C

wire or use No. * AWG,
75

_C wire

Use 60

_C wire, either No. * AWG Cu, or

No. * AWG Al or use 75

_C wire, either

No. * AWG Cu or No. * AWG Al

Use 60

_C wire, No. *

AWG or use 75

_C wire,

No. * AWG

2

60

_C (140_F)

Use No. * AWG, 60

_C

wire

Use 60

_C wire, either No. * AWG Cu or

No. * AWG Al

Use 60

_C wire, No. *

AWG

3

75

_C (167_F)

Use No. *

[ AWG, 75_C

wire

Use 75

_C wire, either No. *[ AWG Cu or

No. *

[ AWG Al

Use 75

_C wire, No.*[

AWG

4

90

_C (194_F)

Use No. *

[ AWG, 90_C

wire

Use 90

_C wire, either No. *[ AWG Cu or

No. *

[ AWG Al

Use 90

_C wire, No.*[

AWG

* The wire size for 60

_C (140_F) wire is not required to be included in the marking. If included, the wire size is based on ampacities for the wire

given in Table 310-16 of the National Electrical Code

r, in ANSI/NFPA 70, and on 115% of the maximum current that the circuit carries under

rated conditions. The National Electrical Code

r is a registered trademark of the National Fire Protection Association, Inc.

[ Use the larger of the following conductors: the same size conductor as that used for the temperature test or one selected using the guidelines in

the preceding footnote.

Figure 7-2

Terminal Markings for Various Temperature Ratings and Conductors

7.3 Load Lead Connections

Load leads being brought into the generator can enter in
a number of different areas. On generators 300 kW and
below the most commonly used is the bottom entry,
where conduit is “stubbed up” into the junction box from
below. Other methods include flexible conduit roughed
into the sides or top of the junction box. When using this
method, be sure not to block the front or rear of the
controller, as doing so will prevent access to it for service
purposes. See Figure 7-3.

On generators larger than 300 kW, a junction box is
mounted on the rear of the generator. Larger sets may
have oversize junction boxes supplied as an option or to
accommodate buss bar connections. Consult the
dimensional

drawing

on

your

unit

for

detailed

information.

TP-5700-7

1

2

1. Conduit from ceiling
2. Conduit stubbed up from below

Figure 7-3

Typical Load Lead Connection

Advertising