Hazardous noise, Hazardous voltage/ electrical shock, Caution – Kohler Generator Sets 20--2800 kW User Manual

Page 7: Danger, Warning

Advertising
background image

TP-5700 7/93

III

Safety Precautions and Instructions

The fuel system.

Explosive fuel

vapors can cause severe injury or
death.

Vaporized fuels are highly

explosive.

Use extreme care when

handling and storing fuels. Store fuels
in a well-ventilated area away from
spark-producing equipment and out of
the reach of children. Never add fuel to
the tank while the engine is running
because spilled fuel may ignite on
contact with hot parts or from sparks.
Do not smoke or permit flames or
sparks to occur near sources of spilled
fuel or fuel vapors. Keep the fuel lines
and connections tight and in good
condition. Do not replace flexible fuel
lines with rigid lines.

Use flexible

sections to avoid fuel line breakage
caused by vibration. Do not operate the
generator set in the presence of fuel
leaks, fuel accumulation, or sparks.
Repair fuel systems before resuming
generator set operation.

Explosive fuel vapors can cause
severe

injury

or

death.

Take

additional precautions when using the
following fuels:

Gasoline—Store

gasoline

only

in

approved

red

containers

clearly

marked GASOLINE.

Propane (LP)—Adequate ventilation
is mandatory.

Because propane is

heavier than air, install propane gas
detectors low in a room. Inspect the
detectors

per

the

manufacturer’s

instructions.

Natural Gas—Adequate ventilation is
mandatory. Because natural gas rises,
install natural gas detectors high in a
room. Inspect the detectors per the
manufacturer’s instructions.

Fuel tanks. Explosive fuel vapors
can cause severe injury or death.
Gasoline and other volatile fuels stored
in day tanks or subbase fuel tanks can
cause an explosion. Store only diesel
fuel in tanks.

Gas fuel leaks.

Explosive fuel

vapors can cause severe injury or
death.

Fuel leakage can cause an

explosion. Check the LP vapor gas or
natural gas fuel system for leakage by
using a soap and water solution with
the fuel system test pressurized to
6--8 ounces

per

square

inch

(10--14 inches water column). Do not
use a soap solution containing either
ammonia or chlorine because both
prevent bubble formation. A successful
test depends on the ability of the
solution to bubble.

Hazardous Noise

Hazardous noise.
Can cause hearing loss.

Never operate the generator set
without a muffler or with a faulty
exhaust system.

CAUTION

Hazardous Voltage/
Electrical Shock

Hazardous voltage.
Will cause severe injury or death.

Disconnect all power sources before
opening the enclosure.

(over 600 volts)

DANGER

Hazardous voltage.
Will cause severe injury or death.

Disconnect all power sources before
servicing.

Install the barrier after

adjustments,

maintenance,

or

servicing.

(over 600 volts)

DANGER

Hazardous voltage.
Can cause severe injury or death.

Disconnect all power sources before
servicing.

Install the barrier after

adjustments,

maintenance,

or

servicing.

(600 volts and under)

WARNING

Hazardous voltage.
Can cause severe injury or death.

Disconnect all power sources before
opening the enclosure.

(600 volts and under)

WARNING

Hazardous voltage.
Can cause severe injury or death.

Operate the generator set only when
all guards and electrical enclosures
are in place.

Moving rotor.

WARNING

Advertising