5 automatic transfer switches, 6 control connections, 7 remote annunciator – Kohler Generator Sets 20--2800 kW User Manual

Page 50: 8 audiovisual alarm, Figure 7-7 audiovisual alarm, Remote annunciator 14-relay dry contact box, Front view side view

Advertising
background image

TP-5700 7/93

38

Section 7 Electrical Requirements

7.5 Automatic Transfer Switches

A typical standby system has at least one automatic
transfer switch connected to the generator set output to
automatically transfer the electrical load to the
generator set if the normal source fails. When normal
power returns, the switch transfers the load back to the
normal power source and then signals the generator set
to stop.

The transfer switch uses a set of contacts to signal the
engine/generator to start. These contacts are terminals 3
and 4 on the generator set controller terminal strip or
controller connection terminal strip (if used) inside the
junction box. When the normal source fails and the
generator set master switch is in the AUTO position, the
transfer switch contacts close to start the generator set.

The location of the transfer switch contacts is usually
near the contactor with an engine start decal to identify
the correct terminals. The terminals are identified as 3
and 4 (or 57 and 58). Do not connect to terminals 57 and
58 on the inner panel circuit board. Connection must be
at the contactor location. Verify the correct engine start
terminals using the transfer switch wiring diagrams
before making connections.

7.6 Control Connections

Most standby generators can be equipped with a myriad
of optional equipment that will have to be connected to
other components in the system. These accessories will
enable the generator set to meet standards for local and
national codes, or specific requirements of the
customer’s installation. A few of the more common
accessories and their functions are listed on the
following pages.

7.7 Remote Annunciator

The remote annunciator allows monitoring of the
standby power system from a location remote from the
generator

set.

Individual

lamps

identifying

fault

shutdowns and/or prealarms are located on the remote
annunciator, along with an alarm horn and silence
switch. There are both surface- and flush-mount models
available. The remote annunciator is typically located in
an area that is monitored on a full-time basis. This allows
the operator to be aware of any alarm conditions when
they occur without having to be physically present at the
generator set. See Figure 7-6.

Remote Annunciator

14-Relay Dry Contact Box

A-293983

A-258782

P

FBA--1

42B

10 AMP

NO C

C

NO

C

NO

C

NO

C

NO

C

NO

C

NO

C

NO

C

NO

C

NO

C

NO

C

NO

C

NO

C

NO

K1

K2

K3

K4

K5

K6

K7

K8

K9

K10

K11

K12

K13

K14

INPUT CONTACT RATINGS: 10A @120VAC RES. LOAD

.01A @28VDC MIN.

10A @28VDC MAX.

PCB ASSY A--320639

LOT NO.

42A 2

K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11

K13 K14

K12

P

N

Figure 7-6

Remote Annunciator with 14-Relay Dry
Contact Kit

7.8 Audiovisual Alarm

The audiovisual alarm warns the operator of a fault
shutdown or prealarm condition at a remote location.
See Figure 7-7.

Front View

Side View

A-292887

Figure 7-7

Audiovisual Alarm

Advertising