Service Manual 34

Troubleshooting Guide

COMPLAINT

CAUSE

REMEDY

Test capacitor.

Check the terminals. If loose, repair or replace.

Check the system for a restriction.

If restricted, clean of replace.

Close if open.

Determine if the unit is properly sized for the area to

be cooled.

Check the set screw or clamp. If loose or missing,

correct. If the blower or fan is hitting air guide,

rearrange the air handling parts.

Remove the cabinet and carefully rearrange tubing

not to contact cabinet, compressor, shroud, and bar-

rier.

Set the knob to HIGH COOL or LOW COOL while

rocker switch is ON.

Check terminals. If loose, repair or replace.

Check the synchronous motor for open circuit.

Capacitor

Wiring

Refrigerating system

Air filter

Exhaust damper door

Unit undersized

Turbo or fan

Copper tubing

Rotary switch.

Wiring

Synchronous motor.

Compressor cycles
on overload.

Insufficient cooling or heat-

ing

Excessive noise.

Auto air-swing fails.