Installation – LG WG1805RY6 User Manual

Page 9

Advertising
background image

Service Manual 8

Installation

Installation

Select the Best Location

Installation Check

How to Secure the Drain Pipe

1.To prevent vibration and noise, make sure the unit is

installed securely and firmly.

2.Install the unit where the sunlight does not shine directly

on the unit.

3.The outside of the cabinet must extend outward for at

least 30cm and there should be no obstacles, such as a
fence or wall, within 50cm from the back of the cabinet
because it will prevent heat radiation of the condenser.
Restriction of outside air will greatly reduce the cooling
efficiency of the air conditioner.

CAUTION: All side louvers of the cabinet

must remain exposed to the outside of
the structure.

4.Install the unit a little slanted so the back is slightly lower

than the front (about 10~15mm). This will help force con-
densed water to the outside.

5.Install the unit from the bottom about 75~150cm above

the floor level.

The setting conditions must be checked prior to initial starting.
The following items are especially important checking points when the installation is finished.

1. Grounding wire (Green or Green and Yellow) is provided in the power cord. The green wire must be grounded.
2. Connect to a single-outlet 15A circuit.

(or 20A circuit for Electric Heater Model)

3. To avoid vibration or noise, make sure the air conditioner is installed securely.
4 Avoid placing furniture or draperies in front of the air inlet and outlet.

In humid weather, excess water may cause the BASE PAN to overflow. To drain
the water, remove the DRAIN CAP and secure the DRAIN PIPE to the rear hole of
the BASE PAN. Press the drain pipe into the hole by pushing down and away from
the fins to avoid injury.

Optional

1. Install the drain pan over the corner of the cabinet where you removed the

plug with 4 (or 2) screws.

2. Connect the drain hose to the outlet located at the bottom of the drain pan.

You can purchase the drain hose or tubing locally to satisfy your particular
needs. (Drain hose is not supplied).

3. Select the most appropriate connection from among the following figures (by

considering the hole of the unit) to fit drain pan to your own unit.

AWNING

COOLED AIR

HEAT

RADIATION

75~15cm

ABOUT 10~15mm

Over 50cm

FENCE

Drain pipe

Drain cap

Fig. 4

Fig. 3

Fig. 2

DRAIN
PAN

DRAIN HOSE

Fig. 1

CABINET

SCREW

Figure 1