Installation

9

5.0

I

NSTALLATION

5.1

Preparation

1. Visually inspect the UPS for freight damage. Report damage to the carrier and your local dealer

or Liebert representative.

2. Decide where to place the PowerSure PSI. Install the UPS indoors in a controlled environment

where it cannot be accidentally turned Off. Place it in an area of unrestricted airflow around the

unit, away from water, flammable liquids, gases, corrosives, and conductive contaminants.

Maintain a minimum clearance of 100mm (4 inches) in the front and rear of the UPS. Maintain an

ambient temperature range of 0°C to 40°C (32°F to 104°F).

3. The PowerSure PSI may be installed in either a tower configuration or in a rack, depending on

available space and use considerations. Determine the type of installation and follow the

appropriate instructions in either Tower UPS Installation or Rack-Mount UPS Conversion

and Installation.

5.2

Tower UPS Installation

When using the PowerSure PSI in a tower configuration, use the included support base (shown below,

left) to stabilize the UPS. If two or more battery cabinets are added, the spacers—included with the

battery cabinets—should be used to accommodate the additional cabinets.

Figure 6

Support base for tower configuration

1. To orient the display for vertical viewing, remove the front plastic bezel by pulling forward evenly

on both sides.

2. Peel the backing from the vertical display overlay and apply to the existing display.
3. Snap the front bezel back into place.

!

CAUTION

The UPS is heavy (see Table 4 - Battery cabinet specifications). Take proper precautions

when lifting or moving it.

NOTE
UPS operation in temperatures above 25°C (77°F) reduces battery life.

Tower Stand - Fully Extended

Spacers Can be Added to Accommodate External Battery Cabinets

Connectors Snap into Slots on Base