Table 4 battery cabinet specifications, Table 4, Battery cabinet specifications – Liebert PSITM User Manual

Page 31

Advertising
background image

Specifications

27

Agency

Safety

EN 62040-1-1; TUV/GS listed; CE compliance mark

Surge

EN61000-4-5, Level 3, Criteria B

ESD

EN61000-4-2, Level 3, Criteria B

Susceptibility

EN61000-4-3, Level 3, Criteria A

Electrical Fast Transient

EN61000-4-4, Level 4, Criteria A

Emissions

EN 50091-2, Class B

Conducted Immunity

EN61000-4-6

Harmonics

EN61000-3-2

Flicker

EN61000-3-3

Transportation

ISTA Procedure 1A Certification

Table 4

Battery cabinet specifications

Model Number

PS2-48VBATT

PS2-72VBATT

Used w/UPS Model

PS1000RT2-230

PS1440RT2-230

PS2200RT2-230

PS3000RT2-230

Dimensions, W x D x H, mm (in)

Unit

87 x 557 x 430 (3.43 x 22 x 17)

87 x 612 x 430 (3.43 x 24.1 x 17)

Shipping

300 x 706 x 598

(11.8 x 27.8 x 23.5)

333 x 864 x 598

(13.1 x 34 x 23.5)

Weight, kg (lbs)

Unit

30 (66.1)

46 (101.4)

Shipping

38.6 (85.1)

53.6 (118.1)

Battery Parameter

Type

Valve-regulated, nonspillable, lead acid

Quantity x Voltage x Rating

2 strings of 4 x 12V x 7Ah

2 strings of 6 x 12V x 9Ah

Battery Manufacturers

CSB, B&B Battery and EnerSys

Backup Time

See Table 5 - Battery run times

Environmental

Operating Temperature

0°C to + 40°C (+32°F to + 104°F)

Storage Temperature

-15°C to + 40°C (+5°F to + 104°F)

Relative Humidity

0% to 95%, non-condensing

Operating Altitude

Up to 3,000m (10,000 ft) at 35°C (95°F) without derating

Agency

Safety

EN 62040-1-1; TUV/GS listed; CE compliance mark

Emissions

EN 50091-2, Class B

Transportation

ISTA Procedure 1A Certification

Table 3

UPS specifications (continued)

Model Number

PS1000RT2-230

PS1440RT2-230

PS2200RT2-230

PS2200RT2-230E

PS3000RT2-230

PS3000RT2-230E

Advertising