3 battery mode, Figure 16 low battery mode, 4 battery recharge operation – Liebert PSITM User Manual

Page 22: Battery mode, Battery recharge operation, Caution

Advertising
background image

Modes of Operation

18

7.3

Battery Mode

The UPS switches to Battery mode in the event of an extreme input voltage/frequency condition or

complete mains failure. The battery system supplies power through the Inverter (1000VA & 1440VA)

or through the DC-to-DC converter to the Bi-Directional Converter (2200VA & 3000VA) to generate

power for the connected equipment.
When the UPS is in Battery mode, the Battery Indicator illuminates green and an alarm sounds

every 10 seconds. As capacity decreases, fewer indicators remain illuminated. Figure 15 shows the

UPS in Battery mode with 61% - 80% battery capacity remaining.

Figure 15 Battery mode at 61 – 80% battery capacity

When a low battery condition occurs, the Battery Indicator flashes green and the alarm sounds every

half-second. The default low battery warning is two (2) minutes but can be configured via MultiLink.

For more information, refer to 11.0 - Troubleshooting.

Figure 16 Low Battery mode

For approximate battery run times, refer to Table 5 - Battery run times. These run times are

approximates based on resistive load and an ambient temperature of 25°C (77°F). To increase this

time, turn Off non-essential pieces of equipment, such as idle computers and monitors, or add exter-

nal battery cabinets.

7.4

Battery Recharge Operation

Once mains power is restored, the UPS resumes normal operation. At this time, the Battery Charger

begins recharging.

!

CAUTION

Turning Off the UPS while it is in battery mode will result in loss of output power.

Battery Indicator

illuminated

Battery Indicator

flashes green

Advertising