Installation

11

4. Attach the two (2) fixed rails to the racks mounting rails. The fixed rail assemblies fit on the

inside of the rack mounting rails.

5. Insert two (2) M5 flat head screws loosely (finger-tight) into the top and bottom holes on the front

of the fixed rail assembly (see Figure 9).

6. Extend fixed rail by sliding inner member backward until it touches the rear rack mounting rail.
7. Insert two (2) M5 screws loosely (finger-tight) into top and bottom holes on the rear of the fixed

rail assembly.

8. Check alignment of fixed rails and tighten all screws to ensure locking action.

Figure 9

Rack mounting rails and slide assemblies

9. Lay the UPS in rack-mounting position on the fixed rails. The UPS should move smoothly forward

and backward on the fixed rails. If not, recheck alignment.

10. Use the extra M5 screws provided, secure front of the UPS to rack mounting rails to prevent the

UPS from sliding out of position.

11. PowerSure PSI 230 VAC models are not supplied with an input power lead for connection to the

mains supply. Additional input/output cords may be obtained from your dealer. The input power

cord must have a minimal cross-sectional area of 1mm

2

.

12. Shut down the load equipment and turn off the mains

supply. Unplug the load equipment's power input

cable from the mains supply socket and plug it into the

UPS input socket.

Plug the power input cable into the mains supply

socket. Connect the supplied IEC-320-C14 output

power cable between the load equipment input socket

and one of the UPS AC output sockets.

13. Connect all load equipment to the UPS in this

manner.

14. Turn On the UPS by pressing the ON button. Check

that the AC Input Indicator is not flashing. If it is

flashing, refer to 11.0 - Troubleshooting. Then turn

On the connected equipment. The UPS is now providing conditioned power to your equipment.

!

CAUTION

Lifting equipment into rack may be a two-person job, depending on weight of equipment.

!

CAUTION

To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables should

be segregated and run separately from power cables.