Installation of decoration panel, Service manual 25 installation – LG LCN240CP User Manual

Page 25

Advertising
background image

Service Manual 25

Installation

5. Installation of Decoration Panel

1. Temporarily fix two decoration panel fixing screws (hexagon M5 screw) on the unit body. (Tighten by

amount 10mm(0.39inch) in length.)
The fixing screws (hexagon M5 screw) are included the indoor unit box.

2. Remove the air inlet grille from the decoration panel. (Remove the hook for the air inlet grille cord.)
3. Hook the decoration panel key hole ( ) on the screws fixed in step above, and slide the panel so

that the screws reach the key hole edge.

4. Retighten completely two temporarily fixed screws and other two screws. (Total 4 screws)
5. Connect the louver motor connector and display connector.
6. After tightening these screws, install the air inlet grille (including the air filter).

Decoration panel fixing screws
(hexagon M5 screws)
Temporally fitting at 2 places
(Tightening about 10mm(0.39inch))

Control box cover

Piping side

Inlet Grille

Inlet Grille

Inlet Grille

Louver motor

Decoration panel fixing screws
(Hexagon M5 screw)

Air conditioner unit

Decoration panel

Key holes

Display

Lead wire for
louver motor and
display

The decoration panel has its installation
direction.

Before installing the decoration panel,
always remove the paper template.

CAUTION

Install certainly the decoration
panel.
Cool air leakage causes sweating.

Water drops fall.

Air conditioner
unit

Ceiling

board

Decoration panel

Decoration
panel

Fit the insulator (this part) and
be careful for cool air leakage

Good example

Air

Cool air leakage

(no good)

Bad example

Ceiling

board

Air conditioner unit

Advertising