40 Ceiling Cassette Air Conditioner

Troubleshooting Guide

Troubleshooting CH03

Check the Volt.

Indoor Unit

V

12Vdc

12V

S

GND

Check the Volt.

Wired R/C

V

12Vdc

12V

S

GND

03

Communication

Wired R/C

• Open / Short
• Wrong connection

• Connection of wire
• Main PCB Volt. DC12V
• Noise interference

Display

code

Title

Cause of error

Check point & Normal condition

Check Point

1. Check the wire connection. (Open / Short)

→ Repair the connection

2. Check the soldering state of connector. (Soldered poorly)

→ Repair or Change the PCB.

3. Check the volt. Of main PCB power source. (DC 12V, DC 5V)

→ Repair or Change the main PCB.

4. Check the installation of wired remote controller. (Noise interference)

→ Adjust the state of installation