Check point – LG LCN240CP User Manual

Page 39

Advertising
background image

Service Manual 39

Troubleshooting Guide

10k

Check the resistance

Check the voltage

V

2.5Vdc

01

02

06

Indoor air sensor

Indoor inlet pipe sensor

Indoor outlet pipe sensor

• Open / Short
• Soldered poorly
• Internal circuit error

• Open / Short
• Soldered poorly
• Internal circuit error

• Open / Short
• Soldered poorly
• Internal circuit error

Normal resistor : 10K

Ω/ at 25°C(77°F) (Unplugged)

Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)

Normal resistor : 5K

Ω/ at 25°C(77°F) (Unplugged)

Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)

Normal resistor : 5K

Ω/ at 25°C(77°F) (Unplugged)

Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)

Display

code

Title

Cause of error

Check point & Normal condition

Check Point

1. Unplug the sensor on Indoor unit PCB.

2. Estimate the resistance of each sensor.

3. If the resistance of the sensor is 10K

Ω/ 5KΩ at 25°C(77°F), then sensor is normal.

4. If the resistance of the sensor is 0 K

Ω or ∞, then sensor is abnormal. → Change the sensor.

5. Plug the sensor on Indoor unit PCB and Power ON.

6. Estimate the voltage of each sensor.

7. If the voltage of the sensor is 2.5Vdc at 25°C(77°F), then sensor is normal.

8. If the resistance of the sensor is 0 or 5Vdc, then sensor is abnormal.

→ Repair or Change the PCB.

Troubleshooting CH01, CH02, CH06