Installation Considerations

2.0

I

NSTALLATION

C

ONSIDERATIONS

Install your Series 600T UPS in accordance with the submittal drawing package and the following

procedures.

A Liebert authorized representative must perform the initial system check-out and start-up to

ensure proper system operation. Equipment warranties will be voided unless system start-up is per-

formed by a Liebert authorized representative. Contact your local Liebert sales representative or

Liebert Global Services at

1-800-543-2378

to arrange for system start-up.

1. Proper planning will speed unloading, location, and connection of the UPS.

Refer to Figure 8

through Figure 55 and Appendix A - Site Planning Data.

2. Refer to information later in this manual regarding the optional Battery Cabinets and

Transformer Cabinets.

Observe all battery safety precautions when working on or

near the battery.

3. Use the shortest output distribution cable runs possible, consistent with logical equipment

arrangements and with allowances for future additions if planned.

4. Recommended ambient operating temperature is 25°C (77°F). Relative humidity must be less

than 95%, non-condensing. Note that room ventilation is necessary, but air conditioning may

not be required. Maximum ambient operating temperature is 40°C (104°F) without derating.

The batteries should not exceed 25°C (77°F). At elevations above 4,000 feet (1219 meters)

derating may be required (consult your Liebert sales representative).

5. Even though your Liebert UPS unit is at least 93% efficient, the heat output is substantial. For

more specific information, see

Appendix A - Site Planning Data.

Be sure environmental

conditioning systems can accommodate this BTU load, even during utility outages.

6. The routing (inside the facility) to the installation site, as well as the floor at the final

equipment location, must be capable of supporting the cabinet weight and the weight of any

moving equipment. The modules weigh between 2775 and 5775 pounds. The battery cabinets

weigh between 3000 and 4900 pounds. The System Control Cabinets weigh between 1000 and

2550 pounds. Refer to

Appendix A - Site Planning Data.

7. Plan the routing to ensure that the unit can move through all aisleways, doorways, and around

corners without risking damage. If the modules and batteries must be moved by elevator, check

the size of the door openings and the weight-carrying capacity of the elevator.

!

CAUTION

Read this manual thoroughly before attempting to wire or operate

the unit. Improper installation is the most significant cause of

UPS start-up problems.

Do not install this equipment near gas or electric heaters. It is

preferable to install the UPS in a restricted location to prevent

access by unauthorized personnel.