4 grounding configurations, battery systems, Figure 6, Battery cabinet grounding configuration – Liebert 600T User Manual
Page 24
Advertising
18
Configuring Your Neutral and Ground Connections
7.4
Grounding Configurations, Battery Systems
Figure 6
Battery Cabinet Grounding Configuration
Large, open-rack battery systems are normally either locally grounded or left ungrounded, depend-
ing on local code requirements.
Battery cabinet systems, on the other hand, should be grounded to the UPS module ground bus.
The figure above illustrates how a simple one-cabinet system would be grounded. For systems with
multiple cabinets, the same configuration would apply. However, for simplicity the installer can
connect all the battery cabinet grounds for a particular module together and run a single ground
conductor to that UPS module ground.