Configuring Your Neutral and Ground Connections

7.4

Grounding Configurations, Battery Systems

Figure 6

Battery Cabinet Grounding Configuration

Large, open-rack battery systems are normally either locally grounded or left ungrounded, depend-

ing on local code requirements.

Battery cabinet systems, on the other hand, should be grounded to the UPS module ground bus.

The figure above illustrates how a simple one-cabinet system would be grounded. For systems with

multiple cabinets, the same configuration would apply. However, for simplicity the installer can

connect all the battery cabinet grounds for a particular module together and run a single ground

conductor to that UPS module ground.