Appendix A - Site Planning Data

12.0 A

PPENDIX

A - S

ITE

P

LANNING

D

ATA

65-225 kVA Multi-Module Systems

12.1

Notes

1. Nominal rectifier AC input current (considered continuous) is based on full rated output load.

Maximum current includes nominal input current and maximum battery recharge current

(considered noncontinuous). Continuous and noncontinuous current limit are defined in NEC

100. Maximum input current is controlled by current limit setting which is adjustable. Values

shown are for maximum setting of 125%. Standard factory setting is 115%.

2. Nominal AC output current (considered continuous) is based on full rated output load.

Maximum current includes nominal output current and overload for 10 minutes.

3. Bypass AC input current (considered continuous) is based on full rated output load.

4. Feeder protection (by others in external equipment) for rectifier AC input and bypass AC input

is recommended to be provided by separate overcurrent protection devices.

5. UPS output load cables must be run in separate conduit from input cables.

6. Power cable from module DC bus to battery should be sized for a total maximum 2.0 volt line

drop (measured at the module) at maximum discharge current.

7. Grounding conductors to be sized per NEC 250-122. Neutral conductors to be sized for full

capacity—per NEC 310-15 (b)(4)—for systems with 4-wire loads and half capacity for systems

with 3-wire loads. NOTE: A neutral conductor is required from each Multi-Module Unit output

to the System Control Cabinet.

8. Rectifier AC Input: 3-phase, 3-wire, plus ground

AC Output to Load: 3-phase, 3 or 4-wire, plus ground

Bypass AC Input: 3-phase, 3 or 4-wire, plus ground

Module DC Input from Battery: 2-wire, (positive and negative)

9. All wiring is to be in accordance with National and Local Electrical Codes.

10. Minimum clearance is 2 feet above UPS.

11. Top or bottom cable entry through removable access plates. Cut plate to suit conduit size.

12. Control wiring and power cables must be run in separate conduits. Control wiring must be

stranded tinned conductors.

13. 7% maximum input harmonic current and 0.92 lagging input power factor at full load with

optional input filter.