Configuring Your Neutral and Ground Connections

17

7.3

Preferred Grounding Configuration with Power-Tie Switchgear

Figure 5

Preferred Grounding Configuration, Power-Tie Systems

Multi-Module Systems can be used with Power-Tie switchgear to provide dual critical load busses.

The Power-Tie switchgear permits transferring critical loads from one critical bus to the other so

that one UPS system and associated breakers can be de-energized for maintenance. Certain config-

urations of Power-Tie equipment also permit the operator to continuously parallel the output of

both UPS systems.

In tied systems, each SCC must have its neutral solidly connected to the Power-Tie switchgear neu-

tral. The UPS modules, as usual, must have their output neutrals solidly connected to their respec-

tive SCC neutrals. There should not be a connection between the service entrance neutral and

either the SCC or module neutrals.

NOTE

It is essential to run a neutral connection between the tie switchgear and

both SCCs as shown in the illustration above.