Configuring Your Neutral and Ground Connections

7.2

Grounding Configuration, 480 or 600 VAC Input and Output, Delta Source

Figure 4

Grounding Configuration with Ungrounded Delta Source Input

As previously mentioned, Series 600T UPS systems require a bypass input neutral for sensing and

monitoring. With a wye-connected input source, the installer should always connected the building

service neutral to the System Control Cabinet (SCC) output neutral to achieve this. When the

building service is delta-connected, however, the installer must take special steps to ensure reliable

UPS functioning.

If building service is ungrounded delta (and there is no intent to operate with one corner of the

delta grounded, either on purpose or accidentally), the SCC requires the Series 600T Artificial Neu-

tral Kit for proper operation. This kit uses a resistor network to create a reference point for the

bypass input. In this case, the SCC output neutral must be bonded to the SCC ground.

If the building service is corner-grounded delta or an Impedance-grounded wye, the SCC requires

the Isolated Neutral Kit, as do each of the UPS modules. This kit uses control isolation transform-

ers to create a reference point. For this application, the SCC output neutral must not be bonded to

the SCC ground.

NOTE

The Artificial Neutral Kit introduces a maximum current of 0.3 amps to

ground. Take care to ensure that this does not interfere with the operation of

any upstream ground-fault detection devices.