Installation, Technical specifications – idealarc® dc-600 vrd – Lincoln Electric IDEALARC IM10018-A User Manual

Page 9

Advertising
background image

60% Duty Cycle

122/61/49

68

A-1

INSTALLATION

IDEALARC® DC-600 VRD

A-1

TECHNICAL SPECIFICATIONS – IDEALARC® DC-600 VRD

Volts at Rated Amperes

44
44
44

Auxiliary Power

See the OPERATION section

for Auxiliary Power

information by model

Amps

600
680
750

Maximum Open Circuit Voltage

5V for 60 HZ models

5V for 50/60 HZ models

Duty Cycle

100% Duty Cycle

60% Duty Cycle
50% Duty Cycle

Output Range

70A/13V-780A/44V (CV)

90A/24V-780A/44V (CC)

INPUT - THREE PHASE ONLY

OUTPUT

1Also called “inverse time” or “thermal/magnetic” circuit breakers; circuit breakers which have a delay in tripping action that decreases as the magnitude of the current increases.

RECOMMENDED INPUT WIRE AND FUSE SIzES

Standard

Voltage

230/460/575/60

415/50/60

CODES

11613, 11707
11598, 11725

100% Duty Cycle

108/54/43

62

50% Duty Cycle

134/67/54

73

Input Current at Rated Output

RATED OUTPUT

INPUT

VOLTAGE /

FREQUENCY

230
460
575
415

TYPE 75°C

(SUPER LAG)

OR bREAKER

SIzE (AMPS)

1

175 Amp

90 Amp
70 Amp

100 Amp

TYPE 75°C

GROUND WIRE

IN CONDUIT

AWG(IEC-MM

2

) SIzES

6 (14)

8 (8.4)
8 (8.4)
8 (8.4)

TYPE 75°C

COPPER WIRE

IN CONDUIT

AWG(IEC-MM

2

) SIzES

30°C (86°F) Ambient

2 (34)
6 (14)

8 (8.4)

6 (14)

INPUT AMPERE

RATING ON

NAMEPLATE

108

54
43
61

HERTz

60
60
60

50/60

PHYSICAL DIMENSIONS

HEIGHT

30.75 in

781 mm

WIDTH

22.25 in

567 mm

DEPTH

39.0 in

988 mm

WEIGHT

525 lbs.

238 kg.