7.0 Site Requirement

© Baxi Heating UK Ltd 2012

7.7

Condensate Drain (cont.)

11. When discharging condensate into a soil stack or waste
pipe the effects of existing plumbing must be considered. If
soil pipes or waste pipes are subjected to internal pressure
fluctuations when WC's are flushed or sinks emptied then
back-pressure may force water out of the boiler trap and
cause appliance lockout.

Boiler

2.5° Minimum fall

iii) Termination to a drain or gully

Boiler

500mm min

2.5° Minimum fall

iv) Termination to a purpose made soakaway

Holes in the soak-away must
face away from the building

50mm per metre of pipe run

50mm per metre of pipe run

Further specific requirements for soakaway
design are referred to in BS 6798.

Pipe must terminate above
water level but below
surrounding surface. Cut
end at 45°