18.0 Fault Finding

Check and correct if necessary
1. The mechanical set of the gas valve
(CO2 values - see instruction)
2. Flame sensing electrode and lead connections
3. Flame sensing electrode position

Flame current should be more than 0.5 • A

Replace PCB

Replace PCB

YES

YES

Replace flame sensing electrode

NO

Check that the supply pressure at

the test point on the gas valve is a

MINIMUM of 17mbar

I

K

Replace safety thermostat

YES

NO

Overheat thermostat operated or

faulty, i.e. continuity across

thermostat terminals

Allow to cool. Continuity

across thermostat terminals

more than 1.5 ohm

J

L

M

Is there 230V at:

Motor 3-way valve

Replace motor 3-way valve

1.

YES

PCB - X3 connector terminals
5 & 6 central heating mode
5 & 7 domestic hot water mode

Replace PCB

2.

NO

Change pump supply cable

YES

Fan connections correct at fan.
PCB - X401 connector terminals 5,6,7 & 8

1.

YES

Replace fan

Temperature sensors faulty.
Cold resistance approximately
10kí @ 25° C (CH sensor)
20kí @ 25° C (Flue sensor)
(resistance reduces with increase in temp.)

NO

Replace sensor

YES

If pump is running the heat exchanger could be
obstructed

Replace heat exchanger

1.

2.

1.

2.

1.