10.0 Installation

© Baxi Heating UK Ltd 2012

Fig. 59

Fig. 58

Cable Clamp

Facia Panel

Terminal Block Cover

10.8

Making The Electrical Connections

NOTE: Both the Live and Neutral connections are fused.

To connect an external control proceed as follows:-

1. Slacken the facia panel securing screws and lift the
outercase panel so that its securing tabs are clear of the
facia. Remove the panel.

2. Completely undo the screws securing the facia panel and
hinge it down (Fig. 58).

3. Undo the terminal block cover securing screw and
remove the cover (Fig. 58).

4. Slacken the unused cable clamp on the LH side of the
boiler chassis (Fig. 59). Insert the external control wiring
through the clamp and route it to the terminal block.

5. Refer to the instructions supplied with the control.

IMPORTANT: The room thermostat MUST be suitable
for 230V switching.

NOTE: An external frost thermostat cannot be used in

conjunction with with the integral timer. The integral
timer can be replaced with the blanking plate supplied in
the installation kit, and wiring connected as in Fig. 61.

6. Remove the link between terminals 1 & 2. The 230V
supply at terminal 2 must be connected to the thermostat.
The switched output from the thermostat must be
connected to terminal 1 (Figs. 60 & 61). If the room
thermostat being used incorporates an anticipator it MUST
be wired as shown in Figs. 60 & 61.

7. Ensure that the external control input cable(s) have
sufficient slack to allow the control box to drop down.
Tighten the cable clamp on the boiler chassis.

8. Replace the terminal block cover, routing the external
control input cable(s) through the second cut-out.

10.9

Preliminary Electrical Checks

1. Prior to commissioning the boiler preliminary electrical
system checks should be carried out.

2. These should be performed using a suitable meter, and
include checks for Earth Continuity,
Resistance to Earth, Short Circuit and Polarity.

b

br

bk

bk

g/y

1

N

L

2

N

N

L

Room ‘Stat

Fused Spur

230V

Fig. 60

b

br

bk

bk

g/y

1

N

L

Frost

Thermostat

External Clock

2

N

N

L

Room ‘Stat

Fused Spur

230V

230V

NOTE: The 230V switched signal for external controls
(Frost Stat - Room Stat - Timer) must always be taken
from terminal 2 at the boiler. Live, Neutral and Earth to
power these controls must be taken from the Fused Spur.

Fig. 61