Set io failsafe, Set io modbus, Set io temperature-scale – Perle Systems 5500208-41 User Manual

Page 78: Set line, Set line service

Advertising
background image

Set Line

78

IOLAN DS1/TS2 CLI Reference Guide, Version 4.1

Set IO Failsafe

Description Sets the failsafe (watchdog) settings for I/O.
User Level Admin
Syntax
Options

mode

timeout

Set IO Modbus

Description Enabling the Modbus option makes the IOLAN act as a Modbus Slave, allowing

Modbus Masters to communicate with the IOLAN to control and/or retrieve I/O data.

User Level Admin
Syntax
Options

mode

uid

Set IO Temperature-Scale

Description Sets the temperature scale that will be used for all Temperature input readings.
User Level Admin
Syntax
Option

temperature-scale

Set Line

Set Line Service

Description Sets the

Line Service

settings to signal I/O. When the line service is set to signal-io,

you also have the option of enabling the I/O extension for the serial singal pins. See

Set

IOChannel IOExtension on page 88

for more information.

User Level Admin
Syntax
Option

signal-io
Sets the line to use signal I/O. You still need to define the serial pins for digital input
(CTS, DSR, or DCD) or digital output (RTS or DTR). See

Set IOChannel Digital

Input (Serial Pins) on page 80

or

Set IOChannel Digital Output (Serial Pins) on page

83

for configuration options.

set io failsafe [mode on|off] [timeout <seconds>]

Enables/disables the Failsafe Timer. This is the global setting that must be enabled to

set the Failsafe Action on the channel for digital outputs and relays. When this timer
expires because of no I/O activity within the specified time interval, the Failsafe Action

set for the channel determines the action on the output.

The number of seconds that must elapse with no I/O activity before the channel

Failsafe Action is triggered. Valid values are 1-9999. The default is 30 seconds.

set io modbus [mode on|off] [uid <1-255>]

Enables/disables the ability to control/monitor I/O channels using the Modbus protocol.

This is the UID you are assigning to the IOLAN, which is acting as a Modbus slave.

set io temperature-scale celsius|fahrenheit

Select the temperature scale that will be used to display temperature data, either
Fahrenheit or Celsius. The default is Celsius.

set line <number> service signal-io