background image

Apx-2

RPS Series: Remote Power Switches - User's Guide

B. Specifications

Power Input / Output:

Model RPS820 (208 to 240 VAC)

AC Input: Two Separate Circuits; 10 Amps Maximum per Circuit

• Voltage: 208 - 240 VAC 50/60 Hz
• Connectors: Two (2) IEC-320-C14 Inlets

AC Outputs:

• Connectors: Eight (8) IEC-320-C13 Outlets, Split into Two 10 Amp Circuits
• Load: 10 Amps per Circuit; providing a Maximum Total of 20 Amps

Model RPS830 (100 to 120 VAC)

AC Input: Two Separate Circuits; 15 Amps Maximum per Circuit

• Voltage: 100 - 120 VAC 50/60 Hz
• Connectors: Two (2) IEC-320-C14 Inlets, Line Cords Supplied

AC Outputs:

• Connectors: Eight (8) NEMA 5-15 Outlets, Split into Two 15 Amp Circuits
• Load: 15 Amps per Circuit; providing a Maximum Total of 30 Amps

Model RPS1620 (208 to 240 VAC)

AC Input: Two Separate Circuits; 10 Amps Maximum per Circuit

• Voltage: 208 - 240 VAC 50/60 Hz
• Connectors: Two (2) IEC-320-C14 Inlets

AC Outputs:

• Connectors: Sixteen (16) IEC-320-C13 Outlets, Split into

Two 10 Amp Circuits

• Load: 10 Amps per Circuit; providing a Maximum Total of 20 Amps

Model RPS1630 (100 to 120 VAC)

AC Input: Two Separate Circuits; 15 Amps Maximum per Circuit

• Voltage: 105 - 120 VAC 60 Hz
• Connectors: Two (2) IEC-320-C14 Inlets, Line Cords Supplied

AC Outputs:

• Connectors: Sixteen (16) NEMA 5-15 Outlets, Split into

Two 15 Amp Circuits

• Load: 15 Amps per Circuit; providing a Maximum Total of 30 Amps

Console / Modem Port Interface:

• Connector: DB9M, RS232C, DTE
• Coding: Serial ASCII, 8 Bits, No Parity