Phonetics Sensaphone ISACC 5000 User Manual

Page 55

Advertising
background image

55

Chapter 7: Programming

Online time out

- When you are online with ISACC locally or remotely, the unit looks for

inactivity. This parameter allows you to set the amount of time, 1 - 255 minutes, that ISACC
will wait during inactivity before it terminates the online session, the default is 4 minutes. If
there is inactivity that meets this parameter, ISACC will disconnect and display the message
TIME OUT on your screen.

Acknowledge on carrier

- When ISACC dials out in data mode, the unit will wait to

receive a carrier signal from a modem. This tells ISACC that a telephone connection has been
made. The acknowledge on carrier parameter allows you to program ISACC to self-acknowl-
edge an alarm when it receives the carrier signal. To acknowledge on carrier, type Y for yes. If
you do not want ISACC to acknowledge on carrier, type N for no. The default is Yes.

When used with the SHOW command, the SYSTEM keyword also displays the following
information in addition to the current values of the above parameters:

Alarm acknowledgment status

- This parameter tells you if any alarms exist and, if so,

whether they have been acknowledged or not. To see which inputs are in alarm, type SHOW
ALARMS.

C program run status

- This parameter will indicate if there is a C program running or not.

Data log status

- This line will indicate if the data logger is currently running.

Current temperature

- ISACC has a temperature sensor on its circuit board. This parameter

will display the current board temperature, not air temperature, in degrees Fahrenheit and
degrees Celsius.

Battery level

- This parameter displays the present voltage of the backup battery, rounded to

the nearest whole number.

AC power status

- This parameter displays the status of the AC power. NOTE: You may use

power outage as a system alarm by controlling it through a C program. See Chapter 8.

To display the current system information and global parameter values, type show system at
an ISACC prompt:

ISACC>show system

SYSTEM INFORMATION

No unacknowledged alarms exist

C program not running

Data logger not running

The temperature is 78 Deg F, 25 Deg C

Battery level is 21 V

AC power is OFF

Unit identification = Snow

Phone number of unit = 555-4592

Data password = 23B79Q4

Network node = 1

Rings until answer = 3

Phone dialing (0=pulse, 1=tone) = 1

Time between calls = 0 Min 30 Sec

Wait time between rounds = 5 Min

Maximum number of calls = 3