Alarm, Data, Alarm data – Phonetics Sensaphone ISACC 5000 User Manual

Page 92

Advertising
background image

92

Sensaphone

®

ISACC Instruction Manual

ALARM

Summary:

int alarm(n);

int n;

Input Number

Description:

The alarm function generates an alarm condition for the input specified by n.

Return value:

The alarm function always returns a zero.

Example:

This program will initiate an alarm 3 condition if input 3 is greater than 100 and input
2 is greater than 90.

main()

{

if ((input(3)>100)&&(input(2)>90))

{

alarm(3);

}

}

NOTE: The Phone numbers, Selection and Dialout in the standard programming parameters
must be set up properly to generate an alarm, or nothing will happen.

DATA

Summary:

int data(n1,n2,n3,n4);

int n1;

Number of hours

int n2;

Number of minutes

int n3;

Number of seconds

int n4;

Start or stop, 0=stop, 1=start

Description:

The data function enables or disables the data logger, and specifies how often the data
logger executes.

Return value:

The data function always returns a zero.

Example:

This program will run the data logger every 2 minutes from 7:00am to 5:00pm, and
disables it at all other hours.

main()

{

if ((hours >= 7) && (hours <= 17))

{

data(0,2,0,1);

}

else

{

data(0,2,0,0);

}

}