Sensaphone

®

ISACC Instruction Manual

OUT_SPEC

Summary:

int out_spec(n);

int n;

Input number

Description:

The out_spec function checks if the value of input n is outside of the high and low
alarm limits. This is without regard to alarm processing, recognition time, acknowl-
edged status, dialout selection, and dialout enabling.

Return value:

The out_spec function will return a zero if the input is within limits, and will return a
nonzero result if it is outside of the limits.

Example:

This program will set output 9, the onboard buzzer, on if input 5 is closed. It will set
output 9 off when input 5 opens again. Input 5 is defined as a normally open input.

main()

{

if (out_spec(5)!=0)

{

output(9,1);

}

}

PUTNUM

Summary:

int putnum(n);

int n;

Value

Description:

The putnum function will write the value of n to the local RS232 port.

Return value:

The putnum function always returns a zero.

Example:

This program will send the value of input 9 to the RS232 port when it is greater than
100.

main()

{

if (input(9) > 100)

{

putnum(input(9));

}

}

NOTE: PUTNUM does not send data to the modem port.