Input terminal pair

COMMON

INPUT

Power supply
terminal block

Wire to the 15V power supply.

POWER

EG 24 24 BAT C 20V C 15V C 12V C 5 V C
AC AC

+

4-20MA

-

4-20mA sensor

4-20mA sensor using internal power supply

4-20mA (externally powered)

- To use an external power supply, wire the positive lead

from the sensor to the positive terminal on the external power source. Wire the negative lead
from the sensor to a numbered input screw on ISACC. Next, connect the power supply to
ISACC by wiring the negative terminal on the power supply to a common screw on ISACC.
See diagram below:

VDC

COMMON

INPUT

+

4-20

mA

-

4-20mA sensor

External power source

Input terminal pair

4-20mA sensor using external power source

0-5V sensor

- To use a 0-5V sensor with ISACC, wire the sensor signal lead to a numbered

input terminal screw on the unit. Then, wire the sensor common to the corresponding com-
mon screw on ISACC. See diagram below:

Input terminal pair

COMMON

INPUT

Signal

0-5V

Common

0-5V sensor

SHIELDED WIRE

ISACC is designed to work in most installations without the need of shielded wire. This does
not apply to wire run in conduit that has other noise-generating conductors such as 60Hz AC.