To wire the logic i/o (right side) to isacc, Dip connector for a 16-module rack, 38 sensaphone – Phonetics Sensaphone ISACC 5000 User Manual

Page 38: Isacc instruction manual, 2i0-4a

Advertising
background image

38

Sensaphone

®

ISACC Instruction Manual

To wire the logic I/O (right side) to ISACC:

1. Attach terminal 1 (on the right side) to 5 VDC on the ISACC power supply termi-
nal block. Attach terminal 2 to one of the C (common) terminals on the ISACC
power supply terminal block.
2. Connect an odd-numbered terminal (3, 5, 7, or 9) to one of the ISACC input
terminals (1-16) on the bottom row terminal block. The shunt for this input must be
in the TEMP position.

To wire the field I/O (left side) to the input device:

If the input device is DC:

1. Connect ground from the outside device to the odd-numbered terminal (3, 5, 7, or
9) on the rack.
2. Connect the positive voltage from the outside device to the even-numbered termi-
nal (2, 4, 6, or 8) on the rack.

If the input device is AC, polarity does not matter and either wire can be connected to a
terminal pair on the rack.

See sample diagram below:

9
8
7
6
5
4
3
2
1

9
8
7
6
5
4
3
2
1

DC input

DC input

2I0-4A

LED

Solid state modules

AC input

AC input

DC device

+

G

DC device

+

G

AC device

AC device

Input devices

POWER

EG 24 24 BAT C 20V C


15V C

12V C 5V C

AC AC

4-module rack

INPUTS

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

Wiring AC and DC input modules using a 4-module rack

DIP CONNECTOR FOR A 16-MODULE RACK

If you need to use all 16 inputs for monitoring AC or DC voltage, you may simplify your
wiring by using a 16-module rack (Potter & Brumfield 2IO16), with a 50-pin ribbon cable
with a card edge connector on one end and a 50-pin socket connector on the other end. The
socket connector connects to the ISACC unit and the card edge connector connects to the

Advertising
This manual is related to the following products: