49

Chapter 5: Outputs

WIRING THE ANALOG OUTPUTS

To wire the analog outputs:

1. Wire the positive terminal on the DC device to a numbered terminal on the analog
outputs terminal block.
2. Wire the negative terminal on the DC device to a common on the analog outputs
terminal block.

See diagram below:

ANALOG OUTPUTS

C 4 C 3 C 2 C 1

DC device

- +

Wiring an analog device

OUTPUT SPECIFICATIONS

DIGITAL:
Output Voltage

0 to 5V

Output Source Current (V = 0V)

-30mA Max

Output Sink Current (V = 5V)

20mA Max

ANALOG:
Output Voltage

0 to 10V

Resolution

8 bits or .03137V

Maximum Total Unadjusted Error

+2 LSB

Voltage Output Slew Rate

3V/

µs

Voltage Output Settling Time

4

µs

Minimum Output Load Resistance (V = 10V)

2K

RELAY:
Type:

SPDT

Rated Load

5A at 120VAC
5A at 30VDC

Carry Current

5A