Sensaphone

®

ISACC Instruction Manual

LIMITS

ISACC allows you to set high and low limits for inputs defined as 4-20mA analog, 0-5V
analog, pulse count, temperature, table, or user defined. The limits are used to determine when
an input is in alarm. The command SET LIMITS prompts you to enter these values. NOTE:
An input defined as N.O. or N.C. does not have a high or low limit. ISACC will display N/A
for that input. An input defined as pulse count can only have a high limit.

To display the current programmed limits, type show limits after an ISACC prompt. You
may display a specific limit by typing show limits followed by the input number.

ISACC>show limits

HIGH AND LOW ANALOG LIMITS

IN01 = "LOW WELL FLOAT " = N/A

IN02 = "HI SUMP FLOAT " = N/A

IN03 = "Input #3 " = N/A

IN04 = "FLOW RATE (GPM) " = LOW = -9999 HIGH = 9999

IN05 = "WELL LEVEL (FT) " = LOW = -9999 HIGH = 9999

IN06 = "RESET " = N/A

IN07 = "Input #7 " = N/A

IN08 = "VOLTAGE " = LOW = -9999 HIGH = 9999

IN09 = "Input #9 " = N/A

IN10 = "Input #10 " = N/A

IN11 = "Input #11 " = N/A

IN12 = "Input #12 " = N/A

IN13 = "Input #13 " = N/A

IN14 = "Input #14 " = N/A

IN15 = "Input #15 " = N/A

IN16 = "Input #16 " = N/A

To program the low and high limits for analog or pulse count inputs, type set limits after an
ISACC prompt. Type a value and press ENTER to go to the next parameter. You may pro-
gram a specific limit by typing set limits followed by the input number.

ISACC>set limits

HIGH AND LOW ANALOG LIMITS

IN01 = "LOW WELL FLOAT " = N/A

IN02 = "HI SUMP FLOAT " = N/A

IN03 = "Input #3 " = N/A

IN04 = "FLOW RATE (GPM) " = LOW = -9999 >0001 HIGH = 9999 >0025

IN05 = "WELL LEVEL (FT) " = LOW = -9999 >0010 HIGH = 9999 >0150

IN06 = "RESET " = N/A

IN07 = "Input #7 " = N/A

IN08 = "VOLTAGE " = LOW = -9999 >0000 HIGH = 9999 >0110

IN09 = "Input #9 " = N/A

IN10 = "Input #10 " = N/A

IN11 = "Input #11 " = N/A

IN12 = "Input #12 " = N/A

IN13 = "Input #13 " = N/A

IN14 = "Input #14 " = N/A

IN15 = "Input #15 " = N/A

IN16 = "Input #16 " = N/A