22

Model 2960/2996 RAS User Manual

2 • Hardware installation

2. Rotate the power cable retainer clip so it secures the power cable plug in the IEC-320 connector as shown

in

figure 7

.

Figure 7. Power cable retainer clip

3. Repeat steps 1 and 2 to install the remaining power cable.

Grounding the Model 2960/2996

Do the following:

1. Assemble a ground wire using #10 AWG wire with green-colored insulation and two ring terminals. Make

the wire long enough to reach one of the following ground sources:

– The building ground rod (generally located at the site’s main service entrance)

– A sprinkler system pipe

– A cold-water pipe

– Building structural steel

2. Install the ground wire between the grounding stud (see

figure 7

) and the grounding source.

To avoid the risk of personal injury, the distance between ground and the
equipment rack must not exceed the distance specified in either local electrical
codes or the National Electrical Code.

UNIT EQUIPPED WITH DUAL SUPPLIES

DISCONNECT BOTH SUPPLIES

BEFORE SERVICING

90-264V

(50-60 Hz)

2 AMP

10/100

ETHERNET

Power cable retainer clip

Grounding stud