8.1 RS-232 Connection (for XVG/eXVG with RS-232 interface)

PC COM Port

(DB9M Connector)

XVG/eXVG Terminal

Block

Wire Color

(If XVG/eXVG is

supplied with optional

harness)

Signal

Pin #

Signal

Pin #

SERIAL RX

2

SERIAL TX

39

WHT/ORN/BLU

SERIAL TX

3

SERIAL RX

40

WHT/ORN/YEL

SERIAL RTN

5

SERIAL RTN

41

WHT/ORN/GRN

Table 14: RS-232 Interface Connection

8.2 RS-485 Connection (for XVG/eXVG with RS-485 interface)

PC COM Port

Through RS232-
RS485 Converter

XVG/eXVG Terminal

Block

Pin #

Signal

Pin #

Wire Color

(If XVG/eXVG is supplied

with optional harness)

TD(B)+

TXD-485A

(SERIAL TX)

39 WHT/ORN/BLU

TD(A)-

RXD-485B

(SERIAL RX)

40 WHT/ORN/YEL

GND (Optional)

SERIAL RTN

41

WHT/ORN/GRN

Table 15: RS-485 Interface Connection

9

XVG/eXVG Modbus Parameters

9.1 Setup Parameters


Set up parameters are write-able parameters used to setup and control all XVG/eXVG
operations. The following notes applied to all parameters:

- Register Number: This is the Modbus address of the register in the XVG/eXVG.
- All registers are readable.
- RO: Read-only. The register is read-only.
- W0: Open access for writing by any user.
- W1: A Customer or Factory level password must be entered before writing is

allowed.

- W2: A password must be entered and IDM_SETUPCONNECT (register no.

3005) set to 1 before writing is allowed.

- W3: A factory level password must be entered before writing is allowed.
- W4: A factory level password must be entered and IDM_SETUPCONNECT set

to 1 before writing is allowed.