4 diagnostics (0x08) (loopback), 8 connections, Diagnostics (0x08) (loopback) – Hamilton Sundstrand Company Fuel Metering Valves XVG User Manual

Page 10: Connections

Advertising
background image

Starting Address Hi 00

Starting Address Hi 00

Starting Address Lo 01

Starting Address Lo 01

Quantity of Registers Hi 00

Quantity of Registers Hi 00

Quantity of Registers Lo 02

Quantity of Registers Lo 02

Byte Count 04

CRC 1008

Registers Value Hi 00

Registers Value Lo 0A

Registers Value Hi 01

Registers Value Lo 02

CRC 9230

Table 12: Modbus Function 16 – Example



7.4.4 Diagnostics (0x08) (Loopback)

Request & Response message:
SLAVE ADDRESS + FUNCTION CODE + SUB-FUNCTION CODE + DATA +
CRC

Request

Length Valid

Value

Slave Address

1 Byte

0 to 247

Function code

1 Byte

0x08

Sub-function 2

Bytes

0x00

Data Any

value

CRC

0x0000 to 0xFFFF

Table 13: Modbus Function 08 - Request & Response Message


An exact copy of the diagnostic query message is sent back as a response.

8

Connections


The XVG/eXVG can communicate via RS-232 or RS-485, one interface or the other.
To communicate with an XVG/eXVG that was built with RS-485 interface circuit, you
may need to use RS232-to-RS485 converter.
The connection from the PC or PLC’s serial port to the XVG/eXVG can be made as
follows:







10