1 general setup parameters, General setup parameters – Hamilton Sundstrand Company Fuel Metering Valves XVG User Manual

Page 12

Advertising
background image


9.1.1 General Setup Parameters

Register
Number

XVG/eXVG Parameter

Name

Write

Access

Description Type

Default

Value

3500 IDM_MODE

W2

Operating Mode: 0=Stroke, 1=Flow
Measurement, 2=Flow Control, 3=Flow
Limiting

U16 0

3501 IDM_PROTOCOL

W2

Bit15=Don’t care, Bit14 = inter-character
timeout enable for Modbus, other bits
reserved

U16

0

3502

IDM_DEMANDSRC

W4

Demand Source, not used

U16 0

3503 IDM_DIGCMDEN

W4

Digital Command Enable: Bit0, 0=Analog,
1=Digital, other bits reserved

U16

0

3504 IDM_SOLMAXAMPS

W4

XView functional flag: 1= XView will allow
parameter download to valve regardless of
demand signal, 2=XView will not download
if Demand>3% (2 is for Solar OEM units)

U16

1

3505 IDM_CURVOLTCFG

W4

Current/Voltage Select: Bit0-Bit5=AI0-AI5,
Bit8-Bit10=AO0-AO2, 0=Current, 1=Voltage

U16

63

3506 IDM_DEMANDOFFST

W4

Demand Offset: ADC counts, range 0-956

U16

683

3507 IDM_POSINTTBLEN

W4

Position Interpolation Table Enable:
0=Disable, 1=Enable

U16

0

3508 IDM_LVDTPHASE

W4

LVDT phase: Range 0-32

U16

8

3509 IDM_AOPOLARITY

W4

Analog Output Polarity: Bit0-Bit2=AO0-
AO2, 0=Positive, 1=Negative

U16

0

3510 IDM_MINDEMAND

W4

=700 if IDM_MODE = 0, 1 or 2,
=600 if IDM_MODE = 3,
Range 600-4000, default represents 4.1mA

U16

700

3511 IDM_VERSION

W4

Valve Type Identifier:

2=Flow Limiting

Mode (Enabled At Factory).

1=Non Flow Limiting

U16

1

3512

IDM_CONFIGNO

W4

Configuration Number: Range 0-65535

U16 102

3513 IDM_VOLTRANGE

W4

I/O Volt Range, Bit format same as
IDM_CURVOLTCFG, 0=0-5V, 1=1-5V/4-
20mA

U16

1

3514 IDM_FLTTM3VOLT3

W4

3.3V fault persist time: x20mS, range 0-
32767

U16

3

3515 IDM_FLTTMINPRES

W4

Input pressure fault persist time: x20mS,
range 0-32767

U16

5

3516 IDM_FLTTMOUTPRES W4

Output pressure fault persist time: x20mS,
range 0-32767

U16

5

3517 IDM_FLTTMLVDT

W4

LVDT fault persist time: x20mS, range 0-
32767

U16

2

3518 IDM_FLTTMTRACK

W4

Tracking fault persist time: x20mS, range 0-
32767

U16

50

3519 IDM_FLTTMGASTEMP W4

Gas Temp fault persist time: x20mS, range
0-32767

U16

50

3520 IDM_FLTTMOVRPRES W4

Overpressure fault persist time: x20mS,
range 0-32767

U16

5

12