10 write modbus application, Write modbus application – Hamilton Sundstrand Company Fuel Metering Valves XVG User Manual

Page 31

Advertising
background image

Register
Number

XVG/eXVG Parameters
Name

Write

Access

Description Type

7072 7073

IDM_FVOLTSNEG15

RO

Fault Log, VoltsNeg15 at time of fault

Float

7074 7075

IDM_TEMPAMB

W3

Approx. ambient temp. of electronics cavity, deg C

Float

7076 7077

IDM_AUTOADCAGAIN

RO

AUTO ADC A gain, range 0.95 to 1.05

Float

7078 7079

IDM_AUTOADCBGAIN

RO

AUTO ADC B gain, range 0.95 to 1.05

Float

7080 7081

IDM_AUTOADCAOFF

RO

AUTO ADC A offset, range -80 to 80 counts

Float

7082 7083

IDM_AUTOADCBOFF

RO

AUTO ADC B offset, range -80 to 80 counts

Float

7084 7085

IDM_VOLTSPOS15

RO

+15V supply voltage, Volts

Float

7086 7087

IDM_VOLTSNEG15

RO

-15V supply voltage, Volts

Float

7088 7089

IDM_XMEAS

RO

Same as PosInInches

Float

7090 7091

IDM_XCMD

RO

Commanded position, inches

Float

7092 7093

IDM_XERR

RO

Position error, inches

Float

7094 7095

IDM_INTXERR

RO

Position control integral command, velocity
(in/0.0001sec)

Float

7096 7097

IDM_VCMD

RO

Velocity command (in/0.0001sec)

Float

7098 7099

IDM_ICMD

RO

Motor current command, counts

Float

7100 7101

IDM_VMEAS

RO

Measured velocity (in/0.0001sec)

Float

7102 7103

IDM_GASTEMPC

RO

Gas temperature in Celsius (includes TempOff), used
for LVDT position compensation & analog output

Float

7104 7105

IDM_MOTORCUR

RO

Motor current, approximation in Amps

Float

7106 7107

IDM_TIT

RO

Total inches traveled

Float

7108 7109

IDM_DJSUM

RO

Total demand jitter, volts

Float

7110 7111

IDM_SLR

RO

Seal life remaining, % (based on IDM_TITHRESH)

Float

7112 7113

IDM_APLUSBV

RO

LVDT A+B voltage measurement

Float

7114 7115

IDM_AMINUSBV

RO

LVDT A-B voltage measurement

Float

Table 22: Real Time Status Parameters

10

Write Modbus Application

Software packages that support Modbus protocol could be used to write Modbus
application for the XVG/eXVG. The necessary Modbus functions are Read
Registers, Write Single Register, and Write Multiple Registers.

- All XVG/eXVG Modbus parameters are readable using Read Register

function.

- Write to the writeable registers can be accomplished with Write functions and

appropriate password.

User Responsibility

By using the Modbus read and write functions, it is possible to access all of the
XVG/eXVG parameters, features, and functions. The following precautions must
be considered when writing your own Modbus application:

31