3 change gas constant r and k procedure, Change gas constant r and k procedure – Hamilton Sundstrand Company Fuel Metering Valves XVG User Manual

Page 34

Advertising
background image

Perform the following steps to retrieve the fault records:

1. Read register 3045, IDM_RECORDS, to get the current number of fault

records available in the XVG/eXVG. The records are named 0, 1, 2, .. , n-1.
Maximum n = 16.

2. To retrieve first record, record 0, write 0 to register 3043,

IDM_FRECORDNO.

3. Write 4 to register 3094, IDM_TESTCTRL.
4. Read registers 3028, 3029, 3044, 5026, 5028, 7050-7072 to complete record

0.

5. Repeat steps 2, 3, 4, and 5, to retrieve record 1, 2, .., n-1.


10.3 Change Gas Constant R and K Procedure

Register
Number

XVG/eXVG Parameter Name

Description

Type

Write

Access

3005 IDM_SETUPCONNECT

Setup Mode: 1=Set Valve in Setup State, 2=Exit
Setup and Reset CPU

U16

W1

3033 IDM_CALFLAGS

Calibration

Flags

U16

W1

3099 IDM_TESTSTR

Test string, used for Modbus write access
password.

U16

W0

7008

IDM_MEASFLOW

Measured Flow, PPH

Float

Read

7518 IDM_CONSTR

R Gas Constant: must be non-zero, default is
Air, 53.34

Float

W0

7520 IDM_CONSTK

K Gas Constant: must be non-zero, default is
Air, 1.4

Float

W0

Table 25: Parameters for Gas Constant R and K

Perform the following steps to change gas constant R and K in real-time.

1. Read registers 7518, 7520, and 7008, to get the R, K, and corresponding

measured flow values. Take note of the R and K values for reference. The
only way to restore the default values without a valve close and reset (engine
shutdown) is to write those values into the valve again.

2. Write registers 7518 and/or 7520 with appropriate new values.
3. Read register 7008 to get new measured flow value.
4. Read the registers that are of interest to your application.
5. If desired, save the new R and K value to the valve. Note that the following

SAVE or RESET procedure will CLOSE and RESET the valve.

SAVE Parameters routine:

- Write a password to register 3099.
- Write 1 to register 3033. Wait 100 milliseconds.
- Write 32 to register 3033. Wait 100 milliseconds.
- Write 1 to register 3005. Wait 100 milliseconds.

34