4 download parameters, 5 re-assign device address procedure, Download parameters – Hamilton Sundstrand Company Fuel Metering Valves XVG User Manual

Page 35: Re-assign device address procedure

Advertising
background image

- Write 2 to register 3005. Valve will close and reset.

6. To restore the previous R and K values, write the value of R to register 7518

and the value of K to 7520. In case the old values are forgotten and the new
values have not been saved to the valve, reset the valve by turning power off
then on to restore R and K. The following steps will also reset the valve; care
must be taken, valve will close and reset.

RESET valve routine:

- Write a password to register 3099.
- Write 1 to register 3005. Wait 100 milliseconds.
- Write 2 to register 3005. Valve will close and reset.

10.4 Download Parameters

All setup parameters, tables 15-20, can be written when you have the appropriate
password. New parameters can be downloaded to the XVG/eXVG as follows:

- Setup proper write-access level for the parameters.
- Write the new values to the registers.
- Perform Save Parameters routine.

10.5 Re-Assign Device Address Procedure

Register
Number

XVG/eXVG Parameter Name

Description

Type

Write

Access

3005 IDM_SETUPCONNECT

Setup

Mode:

1=Set Valve in Setup State, 2=Exit

Setup and Reset CPU

U16

W1

3033 IDM_CALFLAGS

Calibration

Flags

U16

W1

3099 IDM_TESTSTR

Test

string, used for Modbus write access

password.

U16

W0

3540

IDM_SLAVEADDR

Modbus slave address. Range: 1 to 247

U16

W2

Table 26: Parameters Used to Assign Device Address

XVG/eXVG default Modbus address is 1. In case the Modbus address is forgotten,
a new address can be assigned by using broadcast messages. Perform the following
steps; send all messages with device address 0:

1. Make a one-to-one connection between the Modbus master and the

XVG/eXVG; no other Modbus device is present on the network.

2. Write a password to register 3099.
3. Write 1 to register 3005.
4. Write the new device address to register 3540.
5. Write 1 to register 3033. Wait 100 milliseconds.

35