2 write single register (0x06), Write single register (0x06) – Hamilton Sundstrand Company Fuel Metering Valves XVG User Manual

Page 8

Advertising
background image

Example: Request to read holding registers 108 - 110

Request

Response

01 03 00 6B 00 03 74 17

01 03 06 02 2B 00 00 00 64 05 7A

Slave Address 01

Slave Address 01

Function 03

Function 03

Starting Address Hi 00

Byte Count 06

Starting Address Lo 6B

Register Value Hi (108) 02

Number of Registers Hi 00

Register Value Lo (108) 2B

Number of Registers Lo 03

Register Value Hi (109) 00

CRC 7417

Register Value Lo (109) 00

Register Value Hi (110) 00

Register Value Lo (110) 64

CRC 057A

Table 6: Modbus Function 03 - Example



7.4.2 Write Single Register (0x06)

Request message:
SLAVE ADDRESS + FUNCTION CODE + REGISTER ADDRESS + REGISTER
VALUE + CRC

Request

Length Valid

Value

Slave Address

1 Byte

0 to 247

Function code

1 Byte

0x06

Register Address

2 Bytes

0x0000 to 0xFFFF

Register Value

2 Bytes

0x0000 to 0xFFFF

CRC 2

Bytes

0x0000 to 0xFFFF

Table 7: Modbus Function 06 - Request Message



Response message:
SLAVE ADDRESS + FUNCTION CODE + REGISTER ADDRESS + REGISTER
VALUE + CRC

Response

Length Valid

Value

Slave Address

1 Byte

0 to 247

Function code

1 Byte

0x06

Register Address

2 Bytes

0x0000 to 0xFFFF

Register Value

2 Bytes

0x0000 to 0xFFFF

CRC 2

Bytes

0x0000 to 0xFFFF

Table 8: Modbus Function 06 - Response Message